4.2 Ventilation and cooling
• ShopTek compressors require a three foot (one
meter) clearance around their perimeter.
• The location should be free from standing
water.
• Clean air should be supplied to the compres-
sor, free from exhaust and paint fumes, dust,
metal particles, or caustic chemical vapors.
• Hot exhaust air should be vented out of the
area to prevent its recirculation back into the
compressor’s cooling system.
• Ducting or some other means must be used to
ensure that hot exhaust air is vented away from
the compressor if the compressor’s housing
has minimal overhead clearance.
Table 4-1: Ventilation requirements
Model
Ventilation air required
cfm m
3
/hr
ST4 612 1040
ST5 612 1040
ST7 612 1040
ST11 1471 2500
ST15 1471 2500
NOTE
Remove the red shipping straps/shipping studs
before operating the drive assembly. See Figure
4-1 and Figure 4-2.
NOTE
Housing the compressor in an inadequately ven-
tilated enclosure will cause higher compressor
operating temperatures.