Section 5
SEQUENCING TIMERS
32
Summary :
110 Unload pressure -
All machines unload above this pressure regardless of Recovery timer.
108-110 Recovery timer active -
Trim machine will unload after Recovery timer expires.
108 Sequencing unload pressure -
Trim machine unloads above this pressure, Recovery timer starts.
102 Sequencing load pressure -
Next machine in sequence loads below this pressure, Recovery timer
starts.
100-102 Recovery timer active -
Next machine in sequence loads after Recovery timer expires.
100 Load pressure -
All machines load below this pressure, Start Delay timer starts.
70-10 Start Delay Timer active -
Next machine in sequence starts after Start Delay timer expires.
70 Lowest Pressure -
Next machine in sequence starts regardless of Start Delay timer.