113
Start-Up Programming
& Operation
4
4.7 Auto-Tuning
Enter the required information from the motor nameplate. Press
to proceed to the
Auto- Tuning start display.
Note: These instructions continue from Step 7 in “Enter Data from the Motor Nameplate”.
Step Display/Result
1.
After setting T1-07 as illustrated in the previous section, press
and conrm the display is as described below:
2.
Press
to activate Auto-Tuning. ashes.
Note:
The rst digit indicates which motor is undergoing Auto-
Tuning
(motor 1 or motor 2). The second digit indicates the type of
Auto- Tuning being performed.
3. Auto-Tuning nishes in approximately one to two minutes.
◆
Input Data for Auto-Tuning
The T1-
oo
parameters are used to set the Auto-Tuning input data.
Note: 1. Cycling power to the drive will reset the T1-07 (Motor Base Speed), set during the Auto-Tuning
process to factory defaults.
2. For motors that are to be operated in the eld weakening range, rst perform the Auto-Tuning
with the base data, i.e. the frequency at which the motor is operating with its rated voltage (base
frequency). After Auto-Tuning is complete, change the maximum frequency E1-04 to the desired
value.
■
T1-00: Motor 1/Motor 2 Selection
Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input
is set for function H1-
oo
= 16. This parameter is not displayed if motor 1/2 switching is
disabled.
No. Name Setting Range Default
T1-00 Motor 1/2 Selection 1 or 2 1
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E1-
oo
and E2-
oo
for motor 1.
Setting 1: Motor 2
Auto-Tuning automatically sets parameters E3-
oo
and E4-
oo
for motor 2. Make sure
that motor 2 is connected to the drive for Auto-Tuning.