149
Troubleshooting
5
5.4 Operator Programming Errors
5.4 Operator Programming Errors
oPE Codes, Causes, and Possible Solutions
Table 5.4 oPE Codes, Causes, and Possible Solutions
LED Operator Display Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
oPE02
Parameter Range Setting Error
Use U1-18 to nd parameters set outside the range.
oPE03
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function
contact inputs H1-01 to H1-07.
oPE04 Initialization required.
oPE05
Run Command/Frequency Reference Source
Selection Error
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
analog inputs H3-02 through to H3-10 and PID
functions conict.
oPE08
Parameter Selection Error
A function has been set that cannot be used in the
motor control method selected.
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires
that PID control is enabled (b5-01 = 1 to 4).
oPE10
V/f Data Setting Error
One or more of the parameters listed below are not
set according to the formula:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train
(H6-06).
An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an
individual parameter setting is inappropriate.