A.3 Three-Phase 400 V Class Drives
Table A.4 Power Ratings
Item Specication
Three-Phase Drive Model HF5204 A20 A40 A75 1A5 2A2 3A7
Maximum Applicable Motor
Capacity (kW) <1>
HD Rating 0.2 0.4 0.75 1.5 2.2 3.7
ND Rating 0.4 0.75 1.5 2.2 3.0 5.5
Input
Input Current (A)
<2>
HD Rating 1.2 1.8 3.2 4.4 6.0 10.4
ND Rating 1.2 2.1 4.3 5.9 8.1 14.0
Output
Output Current
(kVA) <3>
HD Rating
<5>
0.9 1.4 2.6 3.7 4.2 7.0
ND Rating
<4>
0.9 1.6 3.1 4.1 5.3 8.5
Output Current (A)
HD Rating
<5>
1.2 1.8 3.4 4.8 5.5 9.2
ND Rating
<4>
1.2 2.1 4.1 5.4 6.9 11.1
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency 5 kHz (user-adjustable from 2 to 15 kHz)
Maximum Output Voltage (V) Three-phase power: 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V <6>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
Harmonic Corrective Actions DC Reactor Optional
<1> The motor capacity (kW) refers to a Sumitomo 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
<6> DC is not available for UL standards.