4.5 Application Selection
No. Name Default Setting
E1-03 V/f Pattern Selection 0FH
E1-07 Middle Output Frequency 30.0 Hz
E1-08 Middle Output Frequency Voltage 50.0 V
L2-01 Momentary Power Loss Operation Selection 1: Enabled
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
Table 4.4 Water Supply Pump: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection 1 E1-08 Middle Output Frequency Voltage
b1-02 Run Command Selection 1 E2-01 Motor Rated Current
b1-04 Reverse Operation Selection H1-05
Multi-Function Digital Input Terminal
S5 Function Selection
C1-01 Acceleration Time 1 H1-06
Multi-Function Digital Input Terminal
S6 Function Selection
C1-02 Deceleration Time 1 H1-07
Multi-Function Digital Input Terminal
S7 Function Selection
E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts
E1-07 Middle Output Frequency
Setting 2: Conveyor Application
Table 4.5 Conveyor: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Drive Duty Selection 0: Heavy Duty
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
Table 4.6 Conveyor: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
A1-02 Control Method Selection C1-02 Deceleration Time 1
b1-01 Frequency Reference Selection 1 E2-01 Motor Rated Current