6. Functional block diagram
The functional block diagram is shown in the figure below
7. Battery Management System Specifications
7.1. Basic parameter settings
NO.
Indicator item
Factory
default
parameters
Is it possible to set
Note
1
Cell overcharge
protection
Cell overcharge alarm
voltage
3600mV
Can be set
Cell overcharge protection
voltage
3650mV
Can be set
Cell overcharge protection
delay
4.0S
Can be set
Single
Overvoltage
Protection
Released
overcharge protection release
voltage Cell
3380mV
Can be set
Capacity release
SOC
96%
Can be set
Discharge release
> 1A
2
Cell
overdischarge
protection
Cell over-discharge alarm
voltage()
2700mV
Can be set
After 30
seconds of
over-
discharge
protection, if
it still cannot
recover, it will
enter low
Cell over-discharge
protection voltage
2500mV
Can be set
Monomer over-discharge
protection delay
1.0S
Can be set
Cell over-
discharge
Cell over-discharge
protection release voltage
2800mV
Can be set