20
the target value and the active power value of the grid-connected point, and then the
reactive power can be regulated by energy storage and PV devices.
• If it is set to Logout, the force regulation control function is disabled.
step 3 Click Save to save the configuration.
- - End
1.7.7 Active Power Control
It is used to control the plant to output active power according to the remote protocol or the
fixed target value set on a local Web.
step 1 Click Control Method→Active Control to enter the corresponding interface.
step 2 Click
in Function Commissioning/Ceasing.
• If it is set to Commissioning, the active power control function is enabled, and the
following parameters should be set at this time.
Parameter
Description
Local/Remote
Local
Select Local if there is no need to receive
AGC and AVC scheduling instructions.
It is required to set Set Value, which is the
target value of the active power at the grid-
connected point.
Remote
Select Remote if it is required to receive
AGC and AVC scheduling instructions.
Control Dead
Zone
-
Set the value according to actual conditions.
It limits the range within which the target
active power value can fluctuate. For
example, if the target active power of the
grid-connected point is 10 KW, and the
control dead zone is 5 KW, then the target
active power of the grid-connected point can
range from 5 KW to 15 KW.
The “Local/Remote” in active power control must be set as same as that in
operation parameters. Otherwise, the strategy will not be executed.
• If it is set to Logout, the active power control function is disabled.
step 3 Click Save to save the configuration.
- - End