Step 4 Tighten cartridge to fuse cartridge holder.
Tighten fuse contact flare end against fuse cartridge holder using 50-70 in-lbs (5.65-7.9
Nm) of torque.(Refer to C in "figure 8-8 Remove end plug from fuse cartridge").
Replace end plug on other end of fuse cartridge and tighten to 50-70 in-lbs (5.65-7.9
Nm) torque.(Refer to D and E in "figure 8-8 Remove end plug from fuse cartridge").
Remove end plug and ensure that leaves of tulip tip have spread uniformly (Refer to F in
"figure 8-8 Remove end plug from fuse cartridge").
Replace end plug applying 50-70 in-lbs (5.65-7.9 Nm) torque to both connections (Refer
to D and E in "figure 8-8 Remove end plug from fuse cartridge").
figure 8-9 Fuse link replacement
Failure to properly tighten the fuse cartridge holder and the end plug to the fuse
cartridge will result in a poor electrical connection, resulting in damage to the Bay-
O-Net and the transformer. The steps detailed in ""figure 8-9 Fuse link replacement""
should be followed in proper order to ensure a good electrical connection.
8 Components and Accessories User Manual

Other manuals for Sungrow SC3150UD-MV-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SC3150UD-MV-US and is the answer not in the manual?

Sungrow SC3150UD-MV-US Specifications

General IconGeneral
BrandSungrow
ModelSC3150UD-MV-US
CategoryStorage
LanguageEnglish

Related product manuals