GD_202201_Sungrow SBR HV Battery Parallel Extension Manual_V1.1 Page 5 of 18
© Sungrow Australia Group Pty. Ltd. All rights reserved.
As we continuously improving our services, changes to this document may occur without notice.
1.5 Connection Diagram in Parallel System
•
The COMM terminal of the battery is connected to the COM2 terminal of the combiner
box. Signal cable 1 white and orange cable is used as BMS/CAN_H1; signal cable 2 or-
ange cable is used as BMS/CAN_L1; signal cable 5 white and blue cable is used as
BMS/CAN_H2; and signal cable 6 green cable is used as BMS/CAN_L2.
•
The grounding terminal of the battery is connected to the PE terminal of the combiner box.
•
The COM1 terminal of the combiner box is connected to the PCS. Signal cable 1 white
and orange cable is used as CAN1_H; and signal cable 2 orange cable is used as
CAN1_L.