Controller Operation
Tariff Timer Settings (Spot Timer)
The heat pump is equipped with a Spot Time function, which allows users to customise up to six timer
schedules to take advantage of time-of-use tariffs.
This function can also be used to maximise self-consumption of PV solar energy where the heat pump
is not connected to a compatible solar inverter or energy management system via the PV-Ready
circuit(s).
The following parameters can be adjusted for each timer:
Function
Description
Mode
Select the operating mode (heating / cooling)
Target
Select the target pool temperature
Max Frequency
Select the maximum permissible operating capacity.
(e.g. 100% allows unit to run at normal operating capacity)
Timer On/Off
Select the applicable run times
Days of Week
Select the applicable day(s)
Blue
Timer activated
Grey
Timer deactivated
A total of six timer switch time periods can be set, which can be selected by swiping across to the next
screen using the arrows.
Restricting the running times and maximum frequency may result in a
significant loss of water temperature, and/or an inability to reach the desired
target temperature.
It is recommended that you activate a seven-day timer with the minimum operating
times required to maintain a comfortable baseline pool temperature.
Additional timers can then be added to increase output or raise the target
temperature during times where discounted or self-generated electricity is available.