EasyManua.ls Logo

Superior DRC2035REN - Vent Termination and Clearances

Superior DRC2035REN
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Information
900004-00, 03/2017
Innovative Hearth Products
DRT2000 and DRC2000 Direct-Vent Fireplaces
12
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting
according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or
the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4 - Multiple Terminations
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Roof Pitch Termination Height *
Flat to 6/12 1.0 ft (0.3 m)
6/12 to 7/12 1.25 ft (0.38 m)
7/12 to 8/12 1.5 ft (0.46 m)
8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m)
10/12 to 11/12 3.25 ft (0.99 m)
11/12 to 12/12 4.0 ft (1.22 m)
12/12 to 14/12 5.0 ft (1.52 m)
14/12 to 16/12 6.0 ft (1.83 m)
16/12 to 18/12 7.0 ft (2.13 m)
18/12 to 20/12 7.5 ft (2.29 m)
20/12 to 21/12 8.0 ft (2.44 m)
12
X
Roof pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
discharge
opening
H*
*H = minimum height from roof to
lowest discharge opening of vent
Horizontal overhang
Vertical
wall
Vent
termination
Storm collar
Concentric
vent pipe
Flashing
1” (25.4 mm) minimum
clearance to combustibles
Table 6 - Termination Heights for Vents above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible
projection of 2-1/2” (64 mm) or less (Figure 5). For projections exceeding 2-1/2” (64 mm) (Figure 5). For additional
vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible)
exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all
approved terminations (Table 7).
Figure 5 - Horizontal Vent Termination Clearances
NOTE: See Figure 28
on Page 31 for exterior
wall recess allowances
for compact horizontal
termination.
12”
(305 mm)
minimum
6”
(153 mm)
Termination kit*
6”
Use 6-1/2” for
all horzontal
terminations
applicable
*4” to center of termination for F1797, 8” for 94L10, and 10” for H1968
Combustible projection 2
1/2” or less in length
Combustible projection
greater than 2-1/2” in length
Ventilated
soffi t - 18”
(457 mm)
Unventilated
soffi t - 12”
(305 mm)
6
(152)
Termination kit
*

Related product manuals