TempControl thermostatic mixing valve made from lead
free** metal components. Models 102-700 feature
serviceable integral check stops. Models 900 & 1000
feature removable check stops with union ells (see table 1
for ow rates).
Coordinating Model Numbers
Specification
Modifications (Components Certified Separately)
Warranty
5 Years - for commercial installations.
Refer to www.symmons.com/warranty for complete
warranty information.
Compliance
Note: Append appropriate sufx to model number.
TempControl 7 Series
Operation & Maintenance Manual
7-102, 7-200, 7-400,
7-500, 7-700, 7-900, 7-1000
-NI
-W
Rough nickel finish
Wall mounting bracket
-P
Polished chrome highlight finish
HTA-100
BV-( )
High temp audio/visual alarm system
Volume control shut off valves
T-425-( )
3” bimetal dial thermometer
SV-( )
WHA-1
Solenoid valve
Water hammer arrestor
TF-( )
Tee fittings
Note: Insert proper model number in parenthesis.
Table 1: Flow Rate - gpm (L/min)
Valve Model Min. Flow Rate*
Min. Flow Rate
(per ASSE 1017)
Pressure Differential - psi (kPa)
5 psi
(34 kPa)
10 psi
(69 kPa)
20 psi
(138 kPa)
25 psi
(172 kPa)
30 psi
(207 kPa)
45 psi
(310 kPa)
7-102
0.5 gpm
(1.9 L/min)
0.5 gpm
(1.9 L/min)
1 gpm
(4 L/min)
3 gpm
(11 L/min)
6 gpm
(23 L/min)
7 gpm
27 L/min)
8 gpm
(30 L/min)
11 gpm
(42 L/min)
7-200
0.5 gpm
(1.9 L/min)
5 gpm
(19 L/min)
7 gpm
(27 L/min)
12 gpm
(46 L/min)
18 gpm
(68 L/min)
21 gpm
(80 L/min)
23 gpm
(87 L/min)
27 gpm
(102 L/min)
7-400
0.5 gpm
(1.9 L/min)
9 gpm
(34 L/min)
18 gpm
(68 L/min)
27 gpm
(102 L/min)
37 gpm
(140 L/min)
41 gpm
(155 L/min)
44 gpm
(167 L/min)
53 gpm
(201 L/min)
7-500
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
22 gpm
(83 L/min)
38 gpm
(144 L/min)
50 gpm
(190 L/min)
55 gpm
(209 L/min)
59 gpm
(224 L/min)
70 gpm
(265 L/min)
7-700
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
25 gpm
(95 L/min)
43 gpm
(163 L/min)
57 gpm
(216 L/min)
62 gpm
(235 L/min)
66 gpm
(250 L/min)
77 gpm
(292 L/min)
7-900
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
30 gpm
(114 L/min)
55 gpm
(209 L/min)
76 gpm
(288 L/min)
84 gpm
(318 L/min)
89 gpm
(337 L/min)
104 gpm
(394 L/min)
7-1000
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
38 gpm
(144 L/min)
67 gpm
(254 L/min)
100 gpm
(379 L/min)
111 gpm
(421 L/min)
120 gpm
(455 L/min)
140 gpm
(531 L/min)
*Minimum ow rate when valve is installed at or near the hot water source with recirculated tempered water and continuously operating circulating pump.
**According to US Senate bill S.3874, the term “lead free” is dened as
follows: “not more than a weighted average of 0.25 percent lead when
used with respect to the wetted surfaces of pipes, pipe ttings, plumbing
ttings, and xtures”
Approach temperature:
5°F (2.8°C)
Temperature control range:
70°F - 150°F (21.1°C - 65.6°C)
-ASME A112.18.1/CSA B125.1, CSA B125.3
-ASSE 1017
-NSF/ANSI 61.9, NSF/ANSI 372
7-102 7-200, 7-400
7-500, 7-700
7-900, 7-1000

Questions and Answers:

Symmons 7-102 Specifications

General IconGeneral
BrandSymmons
Model7-102
CategoryControl Unit
LanguageEnglish

Summary

Installation

Piping Diagrams

Illustrates various system piping configurations for TempControl valves.

Operation and Maintenance

Operation and Adjustment

Instructions for adjusting the TempControl valve to the desired temperature.

Maintenance

Procedures for cleaning and maintaining the TempControl valve cartridge.

Cartridge Removal & Replacement

Step-by-step guide for removing and replacing the valve cartridge.

Trouble Shooting Chart

For Tempered Water Recirculated Systems

Troubleshooting common issues in recirculated water systems.

For Tempered Water Non-Recirculated Systems

Troubleshooting issues in non-recirculated water systems.