EasyManua.ls Logo

System Sensor 2012H User Manual

System Sensor 2012H
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
D200-75-00 1 I56-1216-02
2012H Photoelectronic Smoke Detector
with Integral Temp-3 Sounder
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Smoke Detector Description
Smoke detectors are designed to provide early warning of developing fires
at a reasonable cost. They monitor the air and can sense smoke, providing
precious minutes for you and your family to escape before a fire spreads.
Early warning fire detection is best achieved by the installation of fire
detection equipment in all rooms and areas of the household.
Model2012Hisalow-voltagephotoelectronicsmokedetectordesignedfor
open area protection in a residential building. It has a built-in relay which
may be used to activate auxiliary devices such as bells, horns, and door
closers. The relay contacts automatically close 8 seconds after the detec-
tor goes into alarm, and automatically resets approximately 5 seconds
after the alarm stops. A piezoelectric horn in each detector produces an
audible 85 dBA temporal tone evacuation signal when a detector alarms
or an interconnected detector alarms. This temporal tone evacuation sig-
nalcomplieswithUL217.Thesignalconsistsof3beepseach.5seconds
long, spaced .5 seconds apart, followed by 1.5 seconds of silence. These
detectors can be interconnected for a system of up to 12 smoke detectors
per household so when one smoke detector sounds its evacuation signal
it causes the other connected detectors to sound as well.
Installation in Australia Only
The installation temperature range for Australia is to 45°C and has
been tested per the Australian Standard. Ignore installation temperatures
specified for all other applications when installing detectors in Australia.
Detectors should be installed by qualified technicians. Installation of
a main connected power supply unit must be performed by qualified
electricians only. Ignore the power requirements in “Smoke Detector
Requirements” listed below, as these apply to installation in the USA.
The primary power should be provided by a power limited, supervised,
panel type system. A rechargeable battery is required as a backup to the
external power supply in case of a mains failure. In standby operation, the
power limited backup battery (fully charged) must be capable of provid-
ing uninterrupted power for at least 7 days to the system and all smoke
alarms before the panel gives the required low-battery signal. When the
low-battery signal is given, the battery should be capable of providing
power for another 7 days, after which the backup battery should have
enough energy left to allow a 4-minute alarm signal to be given by all
connected smoke alarms.
Smoke Detector Power Requirements (USA)
This smoke detector will not work without power. This smoke detector is
onlyU.L.listedtobepoweredbySystemSensorPartNo.A77-727-01(12-
volt DC power supply). The A77-727-01 must be permanently connected
to the building’s 120-volt AC electrical supply per code. The A77-727-01
will not power the smoke detector if the AC power is cut off for any
reason. The 12-volt DC power supply will only power the detector when
120-volt AC power is present—it is not a power back-up source.
Powerinputratingtothedetectoris12VDC@0.02amps.Input power
totheA77-727-01powersupplymustbefroma24-hour120VAC60HZ
circuit which cannot be turned off by a switch. Power supply and detec-
tor installation must conform to the electrical codes in your area and
Article 760 of the National Electrical Code. It is recommended that
wiring be performed by a licensed electrician.
Smoke Detector Limitations
• This smoke detector is designed for residential use only. System
Sensor does not advise the use of this detector in multiple detector
systems monitored by a central control. This detector is self-restoring
and does not lock into an alarm condition.
• Smoke detectors will not sense a fire if the smoke does not reach
the sensor. In order for a smoke detector to sense smoke, it must be
installed in the immediate vicinity of the fire. In addition, smoke from
fires in chimneys, in walls, on roofs, in remote parts of the building,
or on another level from where the smoke detector is located, may
not reach the smoke detector quickly enough for occupants to escape
unharmed. For this reason, the installer shall install smoke detectors
on every level, in every sleeping area, and in every bedroom of the
household.
• Smokedetectors may not be heard. The alarm horn in this smoke
detector meets or exceeds current Underwriter’s Laboratories stan-
dards.However,ifthesmokedetectorisnotlocatedinthesameroom
as the occupant, or if it is blocked by a closed door or normal noise,
the alarm horn may not be heard. In addition, sound sleepers, or per-
sons who are under the influence of drugs or alcohol may not hear the
alarm or be able to react to it. Therefore, locate this smoke detector,
which has a sounder rated at 85 dB at 10 feet, on every level, in
every sleeping area, and in every bedroom of the household.
In general, detectors may not always warn you about fires caused
by carelessness and safety hazards like smoking in bed, violent explo-
sions, escaping gas, improper storage of flammable materials, over-
loaded electrical circuits, children playing with matches, or arson.
• Smoke detectors are not fool-proof. Like all electronic devices,
smoke detectors have limitations. No type of smoke detector can
sense every kind of fire every time. In addition, smoke from slow,
smoldering fires rises slowly and may not reach the smoke detector
until actual flame breaks out. This type of smoke may not reach the
smoke detector in time for occupants to escape unharmed.
• Smokedetectorsarenotasubstituteforlifeorpropertyinsurance.
Though smoke detectors have been responsible for saving many lives,
they are not warranted or implied to protect lives or property in the
event of a fire.
• To keep your equipment in excellent working order, ongoing mainte-
nance is required per the manufacturer’s recommendations and UL
and NFPA standards. At a minimum, the requirements of Chapter 7 of
NFPA 72, the National Fire Alarm Code, shall be followed. A preven-
tative maintenance agreement should be arranged through the local
manufacturer’s representative. Though smoke detectors are designed
for long life, they may fail at any time. Therefore, smoke detectors shall
be replaced after being in service for 10 years. Any smoke detector, fire
alarm equipment, or any component of that system which fails shall
be repaired or replaced as soon as possible.
Where to Install Smoke Detectors
Warning: As a minimum requirement, smoke detectors must be installed
in accordance with the National Fire Protection Agency (NFPA) Standard
72 which defines the standards for the National Fire Alarm Code (National
Fire Protection Association, Battery march Park, MA 02269-9101). In addi-
tion, observe all local and national building and electrical codes.
Proper Detector Location:
Figure 1: Recommended smoke detector protection for single-
floor residence with only one sleeping area
DINING ROOM KITCHEN BEDROOM BEDROOM
BEDROOMLIVING ROOM
SMOKE DETECTORS FOR MINIMUM PROTECTION
SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
S0144-00
Question and Answer IconNeed help?

Do you have a question about the System Sensor 2012H and is the answer not in the manual?

System Sensor 2012H Specifications

General IconGeneral
BrandSystem Sensor
Model2012H
CategorySmoke Alarm
LanguageEnglish

Summary

Smoke Detector Description

USA Power Requirements

Smoke Detector Limitations

Limitations - Fire Detection

Detectors may not sense fires if smoke does not reach the sensor. Proper placement is crucial.

Limitations - Audibility

Alarm horn may not be heard if detector is distant or blocked. Consider placement and listener conditions.

Limitations - Fire Types

Detectors may not warn of fires caused by carelessness or specific hazards like smoking in bed.

Limitations - Device Imperfections

No detector senses every fire. Slow-smoldering fires may not be detected in time for escape.

Limitations - Insurance

Smoke detectors are not a substitute for life or property insurance.

Maintenance and Lifespan

Regular maintenance and replacement (10 years) are required for optimal performance.

Where to Install Smoke Detectors

General Installation Guidelines

Follow NFPA 72 standards. Install on each story, near bedrooms, and in each sleeping room.

Sloped/Gabled Ceiling Installation

Install 3 feet down on the slant from the highest point of sloped, peaked, or gabled ceilings.

Mounting Locations

Install on ceiling center, or wall 4-6 inches from ceiling if permitted.

Large Room/Hallway Requirements

Detectors needed at both ends of hallways >30 ft, or in rooms >900 sq ft.

Where Smoke Detectors Should NOT Be Installed

Avoid Combustion Particle Areas

Do not install near kitchens, garages, furnaces, or heaters (at least 20 ft away).

Avoid Air Streams and Damp Areas

Keep away from bathrooms, humid areas, and fresh air inlets to prevent nuisance alarms.

Avoid Dead Air Spaces

Do not install in dead air spaces at peaked ceilings or wall/ceiling intersections.

Avoid Fluorescent Light Fixtures

Install detectors at least 10 feet away from fluorescent light fixtures.

Installation Requirements

Electrical Shock Hazard Warning

Turn off power at the main service panel before installation.

Junction Box Specifications

Mount detector to a 4-inch octagonal box; power supply to a 4" square box.

Wiring and Interconnection

Power Supply Wiring

Connect the 12VDC power supply to the building's 120VAC supply.

Interconnect Wiring

Connect signal and ground terminals for up to 12 interconnected detectors.

Maximum Bus Lengths

Refer to chart for maximum power bus length based on wire size and units.

Tamper-Resist Feature

Activate tamper-resist by removing a tab on the mounting bracket.

Detector Mounting and Installation

Mounting Bracket Installation

Install the mounting bracket to the junction box securely.

Detector Attachment

Align arrows on bracket and detector, then rotate to secure.

Power Restoration and Testing

Turn on power, check for green LED flash (1-2 per min), and test each detector.

Connecting Auxiliary Devices with Relay

How to Interconnect Detectors

Interconnection Scope

Interconnect detectors only within one household to prevent nuisance alarms.

System Testing

Test interconnected systems to ensure all units alarm when one is activated.

Testing Information

Weekly Testing Procedure

Test detectors weekly by pressing the test switch for 20 seconds.

Interconnected System Test

Ensure all detectors sound when one is tested; repair if failure occurs.

Warning - Test Method

Never use an open flame to test the detector; use the test switch only.

Detector Status and Monitoring

Normal Operation LED

Green LED flashes 1-2 times per minute indicating normal operation.

Alarm Condition LED

Green LED flashes rapidly when sensing smoke or if a connected detector alarms.

Alarm Causes

Alarm can be from smoke or nuisance sources like cooking smoke or dust.

Cleaning and Maintenance

Safety Precautions

Turn off power before cleaning. Do not attempt internal servicing.

Cleaning Procedure

Vacuum exterior annually or semi-annually with a soft brush attachment.

Service and Warranty

Repair Department

Send defective units to Repair Department, System Sensor, St. Charles, IL.

Three-Year Limited Warranty

Covers defects in materials/workmanship for three years; excludes damage/alterations.

Related product manuals