14
| Electrical connection
Table 14 Tightening torques for various types of bush
Type of bush
1008 1108 1210 1215 1310 1610 1615 2012 2517 3020
Tightening
torque [Nm]
5.7 5.7 20 20 20 20 20 31 49 92
8.3 Assembly tilting device (FTG)
Warning
Danger of injury by tilting the fan during
installation.
The tilting device must be secured in the
opened state by screws in the designated hole
against unintentional folding.
Important
Leaking duct system.
When installing the roof fan and accessories,
all mounting surfaces have to be sealed air
tight.
1.
A
B
2. 3.
E
F
1:5
E
1:5
F
6.5 mm
A
B
9 Electrical connection
Safety information
Warning: Danger from electrical voltage!
Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
Prevent the ingress of water into the connection box.
Electrical connection may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page
2.
Warning: Danger due to electrostatic influence on medical implants!
Persons with medical implants should keep enough distance to the according devices.