| Alarms
GB
Alarm name Explanation Do the following
Supply air fan rpm
Rotation speed of the supply air fan
is lower than minimum required. Fan
malfunction.
Alarm stops the unit.
Check quick connectors of the fan.
Contact your installation company or
place of purchase.
Extract air fan rpm
Rotation speed of the extract air fan
is lower than minimum required. Fan
malfunction.
Alarm stops the unit.
Check quick connectors of the fan.
Contact your installation company or
place of purchase.
Supply air fan control error
Flow or pressure alarm for supply air.
The pressure is bellow pressure limit.
Alarm stops the unit.
Check that air tube for pressure
sensor is connected properly and
cable is not damaged.
Contact your installation company or
place of purchase.
Extract air fan control error
Flow or pressure alarm for extract
air. The pressure is bellow pressure
limit.
Alarm stops the unit.
Check that air tube for pressure
sensor is connected properly and
cable is not damaged.
Contact your installation company or
place of purchase.
Fire alarm
Fire alarm is active.
Alarm stops the unit.
Once the external Fire alarm is
disabled alarm has to be
acknowledged and unit restarted.
Emergency thermostat
Indicates triggered overheat
protection (in case of installed
electric re-heater battery).
A triggered manual or automatic
overheat protection (EMT) gives an
alarm in the control panel.
In case a manual overheat protection
is triggered, reset it by pushing the
reset button.
If the automatic overheat protection
is triggered, it will reset
automatically once the temperature
has dropped.
If the problem continues contact
your installation company or place of
purchase.
Bypass damper
Indicates malfunction in bypass
damper.
Disconnect the main power supply
for 10 seconds to reset control
function.
Power up the unit, an automatic
bypass damper test will be
performed.
If the alarm occurs again after
approximately 2 minutes contact
your installation company or place of
purchase.
Rotor guard
Indicates a rotor malfunction.
No rotation guard signal for 180
seconds.
If the rotating heat exchanger has
stopped. Check the rotor belt.
If the heat exchanger is still rotating,
check that the quick connector for
the sensor is connected and that
there is an air gap of 5-10 mm
between the sensor and the magnet.
Adjust the gap if necessary.
If the alarm persists, the rotor sensor
may be faulty. Contact your
installation company or place of
purchase.