Supplying the unit with a line with an unbalance exceeding the acceptable value results in
cancelling the warranty.
Caution
Correction of the excessive centralized power factor (>0.95) may generate transient phenomena
dangerous for the motors and contactors of the unit during the start and stop phases. Check
instant voltages during these phases.
Caution
23SysAqua
The supply cables of the units must be routed up to the section
switch through the grommets present on the front panel of the units.
Maximum cross-section of the power supply cables: 35mm²
copper cable only
To ensure proper contact, t the end pieces adapted to the cross-
section of the connecting cable.
These units are equipped with a local switch used as general terminal board.