34 SYSHRW
17.1.3. INSUFFICIENT COOLING OR HEATING PRODUCTION
1. Check that the thermostat is properly located in the zone to be heated or cooled and that it is not
near to a source of cold or heat that may inuence the reading.
2. Check the proper operation of the Return Air Temperature (RT) sensor, located on the n exchanger.
3. Airow is insufcient. Check for clogged lters. Clean and replace as required.
4. The cycle inversion valve may be defective and be creating a refrigerant by-pass. If the unit does not
produce heat, check the wiring of the inversion valve coil.
5. Check the proper operation of the pressure relief valve.
6. Measure the water ow on the water loop.
7. Check the conguration of the appliance.
17.1.4. INSUFFICIENT WATER FLOW AT THE LEVEL OF THE PLATE EXCHANGER.
1. Check for proper water circulation at the level of the water circulation pump.
2. If a valve is tted to the water loop, check that it is open.
3. Check that air is not being sucked into the hydraulic system. Bleed the system if required.
17.1.5. APPEARANCE OF WATER DROPLETS IN THE APPLIANCE
1. Check that the condensates drainage pipe is not blocked and that water drains away normally.
2. Check the correct operation of the condensates tray anti-overow oat (Refer to «Alarm codes»
chart).
3. Check that the oat moves freely on its rod. If this is not the case, clean the tray and the oat.
4. Check the cleanliness of the lters.
17.1.6. APPEARANCE OF ABNORMAL NOISES AND VIBRATIONS IN THE CASING
1. Check that the turbine is not rubbing against the scroll and that the latter is not damaged. Replace as
required.
2. Check that the turbine has not worked loose on its shaft. Centre the turbine and tighten it as
required.
3. Check that the compressor is mounted correctly on its shock pads.
4. Check that no part of the turbine rubs against the compressor or any other surface. Reposition
slightly as required.
5. Check that all the attachment screws are tightened properly.
6. Check that air is not being sucked into the hydraulic system.
7. Test that the relays open and close correctly. Replace as required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir SYSHRW Series and is the answer not in the manual?

SystemAir SYSHRW Series Specifications

General IconGeneral
BrandSystemAir
ModelSYSHRW Series
CategoryHeat Pump
LanguageEnglish

Related product manuals