Technical data |
38
Table 6 Electrical data
Model Electric input #1 - Fans Electric input #2 - heating coil
Voltage (V)
Total Power
(kW)
Total Current
Draw (A)
Installation
Fuse (A)
1
SC/TC Voltage (V)
Heater #
Total Power
(kW)
Total Current
Draw (A)
Installation
Fuse (A)
Topvex SC/TC20 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
20 400V 3~ V1
4,2 6,1
10
Topvex SC/TC20 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
20 400V 3~ V2
6,5 9,4
13
Topvex SC/TC20 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
20 400V 3~ V3
9,6 13,9
16
Topvex SC20 None, HWH, HWL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
- - - - - -
Topvex SC/TC25 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
25 400V 3~ V2
6,5 9,4
13
Topvex SC/TC25 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
25 400V 3~ V3
9,6 13,9
16
Topvex SC/TC25 EL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
(16)
25 400V 3~ V5
11,8 17,1
20
Topvex SC25 None, HWH, HWL
400V 3~
(230V 1~)
1,64
4,4
(8,4)
10
- - - - - -
Topvex SC/TC35 EL
400V 3~ 2,28 3,8 10 35 400V 3~ V4 7,2 10,4 13
Topvex TC35 EL 400V 3~ 2,28 3,8 10 TC 35 400V 3~ V5 11,8 17.1 20
Topvex SC35 EL 400V 3~ 2,28 3,8 10 SC35 400V 3~ V5 12,6 18,2 25
Topvex SC/TC35 EL
400V 3~ 2,28 3,4 10 35 400V 3~ V6 18,1 26,1 32
Topvex SC35 None, HWH, HWL 400V 3~ 2,28 3,8 10
- - - - - -
Topvex SC/TC60 EL
400V 3~ 4,88 8,4 16 60 400V 3~ V7 9,6 13,9 16
Topvex SC/TC60 EL
400V 3~ 4,88 8,4 16 60 400V 3~ V8 16,2 23,4 32
Topvex SC/TC60 EL
400V 3~ 4,88 8,4 16 60 400V 3~ V9 32,4 46,8 63
Topvex SC60 None, HWH, HWL 400V 3~ 4,88 8,4 16
- - - - - -
Topvex SC/TC70 EL
400V 3~ 4,88 8,4 16 70 400V 3~ V8 16,2 23,4 32
Topvex SC/TC70 EL
400V 3~ 4,88 8,4 16 70 400V 3~ V9 32,4 46,8 63
Topvex SC70 None, HWH, HWL 400V 3~ 4,88 8,4 16
- - - - - -
1
Included controller 10A