FY operation manual 34
10.9 LEVEL_3 Parameter
Alarm special function setting
(Please refer to Chapter 12.2)
Protocol selection
0 : TAIE
1 : RTU
(Please refer to communication manual)
Data format
0 : O_81
(parity bit=odd, stop bit=1)
1 : O_82
(parity bit=odd, stop bit=2)
2 : E_81
(parity bit=even, stop bit=1)
3 : E_82
(parity bit=even, stop bit=2)
4 : N_81
(parity bit=none, stop bit=1)
5 : N_82
(parity bit=none, stop bit=2)
Baud rate
0 : 24(2400)
1 : 48(4800)
2 : 96(9600)
3 : 192(19200)
4 : 384(38400)
5 : 576(57600)
6 : 1152(115200) bps
PV bias
PV = PV x (PVOH / 5000) + PVOS
Unit
Change this parameter USPL&LSPL
will be reset
0 : °C
1 : °F
2 : U (Linear signal)
PV digital filter
The PV filter is used to eliminate noise
against the measured input
Unit : second
Use for motor valve feedback value
Control action selection
0 : HEAT reverse action
1 : COOL direct action
Super SV function, suppressing overshoot
0 : OFF
1 : ON
Power frequency
0 : 50HZ
1 : 60HZ