10. Installation manual
10.1 Installation Details
Connecting pipe length
Model
Pipe size(Inch)
Liquid
Gas
TAC-09CHSA/XA31 INVERTER
1/4
3/8
TAC-12CHSA/XA31 INVERTER
1/4
3/8
TAC-18CHSA/XA31 INVERTER
1/4
3/8
TAC-24CHSA/XA31 INVERTER
1/4
1/2
Mode
Standard
length: m
Refrigerant piping
Max. length: m
A
Additional refrigerant
Calculation: ×g=20g/m(A-5m)
TAC-09CHSA/XA31 INVERTER
5.0
15
20g/m
TAC-12CHSA/XA31 INVERTER
5.0
15
20g/m
TAC-18CHSA/XA31 INVERTER
5.0
15
30g/m
TAC-24CHSA/XA31 INVERTER
5.0
15
30g/m
Connecting cables
The power cord should be selected according to the following specifications sheet.
Appliance Amps
Wire Size
5
AWG21/0.75 mm2
10
AWG18/1.0 mm2
13
AWG15 /1. 5 mm2
18
AWG14/1.6 mm2
25
AWG12/2.0 mm2
30
AWG10/2.5 mm2
Outdoor unit
In doo r unit
Pi pe length is
15 meters Max.
be less than 5m
Height should
Outdoor unit
Indoor unit
Pipe l ength is
15 meters Max.
be less than 5m
Height should