4).If the piping is installed to the right, the pipes, 
power cable and drain hose must be lagged and 
secured onto the rear of the unit with a pipe 
connection. 
z Insert the pipe connection into the relative slot. 
z Press to join the pipe connection to the base. 
10.2.8 Electronic  connections 
1. Take the cover away. 
2. Connect the cable wires to the terminal board 
using the same numbering as in the indoor unit. 
3. For the electrical connections, see the wiring 
diagram on the back of the cover 
4.  Fasten the cables with a cable-clamp. 
5.  An efficient earth connection must be ensured. 
6.  Replace the covers. 
10.2.9 Connecting  the  pipe 
Screw the flare nuts to the outdoor unit coupling 
with the same tightening procedures described for 
the indoor unit. 
Note: If the tightening torque is not sufficient, there 
will probably be some leakage. With excessive 
tightening torque there will also be some leakage, 
as the flange could be damaged. 
10.2.10 Bleeding 
Air and humidity left inside the refrigerant circuit  can 
cause compressor malfunction. After having 
connected the indoor and outdoor units, bleed the 
air and humidity from the refrigerant circuit by using 
a vacuum pump. 
The air and humidity left inside the refrigerant 
circulation can cause compressor malfunction. 
After having connected the indoor and outdoor 
units, bleed the air and humidity from the 
refrigerant circulation using a vacuum pump. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Wiring diagram on the back of the cover
 
 
Screw 
Remove the upper
 
cover 
Outdoor unit 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
connection pipes
flare nuts
liquid tap
gas tap
indoor unit
protection caps
Li
quid valve
gas valve
service port nut
tap
vacuum pump
service port