ON/OFF select / disable heat counter (ex works = OFF)
SSL Sensor input for supply line temperature (ex works = S4)
Setting range: S1 to S6 Input of the flow sensor
E1 to E9 Value from external sensor via DL
SRL Sensor input for return line temperature (ex works = S5)
Setting range: S1 to S6 Input of the return sensor
E1 to E9 Value from external sensor via DL
VSG Sensor input for volume flow encoder. (ex works = --)
The pulse encoder
VSG can only be connected to input S6. For this purpose the
following settings must be made in the
SENSOR menu without fail:
S6 VSG Volume flow sensor with pulse encoder
LPP Litres per pulse
Setting range: VSG S6 = volume flow encoder
at input 6.
VSG E1 to E9 = Value from external sensor
via DL-Bus
VSG -- = no volume flow encoder
fixed volume flow. For the
calculation of the heat amount, the set volume flow is only used if
the set output is active
V Volume flow in litres per hour. If no volume flow encoder has been set, a fixed
volume flow can be preset in this menu. If a set output is not active, the volume
flow is assumed to be 0 litres/hour.
As activated speed control can produce constant changes in volume flow, this
method is not suited to use with speed control. (ex works = 50 l/h)
Setting range: 0 to 20000 litres/hour in increments of 10 litre/hour
OP Assigned outputs. The set/measured volume flow is only used to calculate the
heat quantity if the output specified here is active (or at least one of several
outputs). (ex works = --)
With pump-valve systems, the allocated outputs must be adjusted according
to the basic diagram (e.g. with program 49: OP 12)
Setting range: OP = -- heat quantity is calculated without any consideration to the
outputs.
Combinations of all outputs (e.g. OP 1, OP 23, OP 123)
SA Share of antifreeze in the heat transfer medium. An average has been calculated
from the product specifications of all of the major manufacturers; this average is
used in the table of mixing ratios. This method generally produces an additional
maximum error of one percent. (ex works = 0%)
Setting range: 0 to 100% in increments of 1%

Table of Contents

Other manuals for Technische Alternative UVR61-3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Technische Alternative UVR61-3 and is the answer not in the manual?

Technische Alternative UVR61-3 Specifications

General IconGeneral
BrandTechnische Alternative
ModelUVR61-3
CategoryDryer
LanguageEnglish