86
Collector cooling function COOLF
With the aid of this function the cylinder is allowed to cool overnight so that the following
day heat can be taken in again.
If the selected sensor (cylinder temperature) has exceeded the set threshold temperature
the selected output remains switched on during the specified period for so long until it is
under-run again. Since even with reduced speed sufficient cooling is achieved excessive
power consumption can be avoided by specifying a speed stage at output O1.
ON/OFF Monitored sensor Nominal value
Release time Block time Affected outputs
Speed stage
(only output 1)
ON / OFF Collector cooling function ON /OFF (ex works = OFF)
SENS Monitored (cylinder) sensor
Setting range: S1 to S6 (ex works = S1)
DV This nominal value must be exceeded by the set sensor.
Setting range: 0 to 150°C in 1°C increments (ex works = 80°C)
Time from which the set outputs are enabled (ex works = 22:00)
Setting range: 00:00 to 23:50 in 10 min increments
Time from which the set outputs are disabled (ex works = 06:00)
Setting range: 00:00 to 23:50 in 10 min increments