The following settings are only possible in
0-10V and PWM modes.
Warning! The values in the following description are by way of example only; they must, in
all cases, be matched to the system!
Control output Output for release Absolute value
control
Desired value for
abs. value control
Differential control
system
Desired value for
Differential control
Event
control system
Desired value of the event Desired value of the
control system
Proportional part Integral part Differential part
Output mode
0-100 or 0-100
Minimum
Analogue stage
Maximum
Analogue stage
Delay time Current
Analogue stage
Setting of test
analogue stage
In this menu the parameters for the control output are specified.
As analogue output it can put out a voltage of 0 to10V in 0.1V increments.
As PWM a digital signal with a frequency of 500 Hz (level approx.10 V) and a variable duty
cycle from 0 to 100% is created.