7300CV MODBUS COMMUNICATION PROTOCOL
File No. :PC-CV-08
Version : 1.A
Page :
23/34
6.5 Inverter Control
6.5.1 Command Data (Readable and Writable)
Register No. Content
101H
Operation Signal
Bit Description 1 0
0 Operation Command Run Stop
1 Reverse Command Reverse Forward
2 External Fault Fault (EFO)
3 Fault Reset Reset
4 Jog Command Jog
5 Multi-function Command S1 ON OFF
6 Multi-function Command S2 ON OFF
7 Multi-function Command S3 ON OFF
8 Multi-function Command S4 ON OFF
9 Multi-function Command S5 ON OFF
A Multi-function Command S6 ON OFF
B Multi-function Command AIN ON OFF
C Multi-function Command RY1 ON OFF
D Multi-function Command RY2 ON OFF
E (Not used)
F (Not used)
102H
Frequency Command
103H~11FH
(Reserved)
Note: Write in zero for Not used BIT, do not write in data for the reserved register.