7300CV MODBUS COMMUNICATION PROTOCOL
File No. :PC-CV-08
Version : 1.A
Page :
25/34
Register No. Content
Bit Description 1 0
0 Terminal S1 Closed Opened
1 Terminal S2 Closed Opened
2 Terminal S3 Closed Opened
3 Terminal S4 Closed Opened
4 Terminal S5 Closed Opened
5 Terminal S6 Closed Opened
Sequence input
status
6 Terminal AIN Closed Opened
7~9 (unused)
A
Multi-function
output1(RELAY1)
ON OFF
B
Multi-function
output 1(RELAY2)
ON OFF
Contact output
C~F (unused)
122H
0123H
Frequency command
0124H
Output frequency
0125H
Output voltage command (1/1V)
0126H
Output DC voltage command (1/1V)
0127H
Output current (10/1A)
0128H
Reserved
0129H
Output torque
012AH
PID Feedback value (100% / Max output frequency, 10/1% )
012BH
PID input value (100% / Max output frequency, 10/1% , sign attached)
012CH
TM2 AIN input value (1024 / 10V) *1
012DH
TM2 AV2 input value (1024 / 10V) *1
Note: Write in zero for Not used BIT