22
* *If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Note: For standard H & C type frame 1, the DO2
function is setting by 03-12.
Group 04: External Analog Input and
Output Parameters
Code
Parameter
Name
Setting Range
Default
Attrib
ute
04-00
AI Input
Signal Type
0: AI1:0~10V
AI2:0~10V
1
1: AI1:0~10V
AI2:4~20mA
2: AI1: -10~10V
AI2: 0~10V
3: AI1: -10~10V
AI2: 4~20mA
4: AI1: 4~20mA
AI2: 0~10V
*9
5: AI1: 4~20mA
AI2: 4~20mA
*9
04-01
AI1 Signal
Scanning and
Filtering Time
0.00~2.00 0.03
04-02 AI1 Gain 0.0~1000.0 100.0 *1
04-03 AI1 Bias -100.0~100.0 0 *1
04-04 Negative AI
0: Disable
0 Note4
1: Enable
04-05
AI2 Function
Setting
0: Auxiliary
Frequenc
0
1: Frequency
Reference Gain
2: Frequency
Reference Bias
3: Output
oltage Bias
4: Coefficient of
cceleration and
Deceleration
Reduction
5: DC Braking
Current
6: Over-Torque
Detection Level
7: Stall
Prevention Level
During Running
8: Frequency
Lower Limi
9: Jump
Frequency 4
10: Added to AI1
11: Positive
torque limi
12: Negative
torque limi
13: Regenerative
Torque Limi
14: Positive /
Group 04: External Analog Input and
Output Parameters
Code
Parameter
Name
Setting Range
Default
Attrib
ute
Negative Torque
Limit
15: Torque
Reference/
Torque Limit (in
Speed Control)
16: Torque
Compensation
17: PTC
Overheat
Protection
04-06
AI2 Signal
Scanning and
Filtering Time
0.00~2.00 0.03
04-07
AI2 Gain
0.0~1000.0 100.0 *1
04-08
AI2 Bias
-100.0~100.0 0 *1
04-09
AI Input
Signal Type
of I/O card
0: AI3: 0~10V
0 *10
1: AI3: -10~10V
2: AI3: 4~20mA
04-10
AI3 Function
Setting
Range and
definition are the
same as those of
04-05
10 *10
04-11
AO1 Function
Setting
0: Output
Frequency
0
1: Frequency
Command
2: Output
Voltage
3: DC Voltage
4: Output
Current
5: Output Power
6: Motor Speed
7: Output Power
Factor
8: AI1 Input
9: AI2 Input
10: Torque
Command
11: q-axis
Current
12: d-axis
Current
13: Speed
Deviation
14: Reserved
15: ASR Output
16: Reserved
17: q-axis
Voltage
18: d-axis
Voltage
19~20: Reserved
21: PID Input