4-19
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
00-00
Control Mode
Selection
0: V/F
0 - O O O O O O O *3
1: V/F+PG
2: SLV
3: SV
4: PMSV
5: PMSLV
6: SLV2
00-01
Motor’s Rotation
Direction
0: Forward
0 - O O O O O O O *1
1: Reverse
00-02
Main Run
Command Source
Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
4: RTC
Note8
00-03
Alternative Run
Command
Selection
0: Keypad
0
(Note4)
- O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
4: RTC
Note8
00-04 Language
0: English
0 - O O O O O O O
*7
1: Simplified Chinese
2: Traditional Chinese
3: Turkish
00-05
Main Frequency
Command Source
Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Analog 1)
2: Terminal Command
UP/DOWN
3: Communication
Control (RS-485)
4: Pulse Input
5: Reserved
6: RTC
Note8
7: AI2 Auxiliary
Frequency
8: Manual Pulse
Generator (MPG)
Note4
00-06
Alternative
Frequency Source
0: Keypad
0
(Note4)
- O O O O O O O
1: External Terminal
(Analog 1)

Other manuals for TECO A510s Series