3.8.2 General Wiring Diagram (For Enhanced E & G type)
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
P2/B1
B2 *1
3Ø Induction motor
E
Main Power Sec tion
+10V: Power for Analog Input
(max. 20mA)
AI1: Multi-Fun ction Analog In put
AI2: Multi-Fun ction Analog In put
PI Pulse In put 32kHz M ax.
S1
DOG
Multi-Fun ction al tran sistor
digital outputs
Op en Collecto r, 48 V
@50mA
(op to-isolat ed)
(R1A)
(R1C)
(R1B)
NC
NO
Multi-Function
Relay Output
External
Analog
Inputs
Digital Input
Section
+
-
Contact rating:
250 VA C < 1.0A
30 VDC < 1.0A
-
Ground
< 100
Ana log
Output 1
Ana log
Output 2
AO1
AO2
GND
An al og Ou tpu ts
AO 1 : 0 – 10 VDC
AO 2 : 0 – 10 VDC / 4-20 m A
DO1
S2
S3
S4
S5
S6
S7
S8
24 V Powe r t er min al fo r di gita l signa l (sou rce)
A510s
Multi-
Fun ction al
Digital I nputs
External base block
Jog Command
Multi-Step Speed Ref. 3
Fault Reset
Multi-Step Speed Ref. 2
Multi-Step Speed Ref. 1
FWD / STOP
REV / STOP
Factory Default
RS485
Communication Port
L2(S)
L3(T)
AC Input Voltage
Braking Resistor
Note 1
R2A
R2C
24VG Digi tal sign al co mmo n (sink)
GND: An alog Sig na l Commo n
-10V: Power for A nalog Inp ut
Pu lse Input
0V
4 ~ 20m A / 0 ~ 10V
-10V ~ 0 ~ 10V / 4~20mA
SF1
SF2
Run Pe rm issive Inpu t
SOURCE PNP
SI NK NPN (DEFAULT)
SW6
P
P
P
CN6 (RJ45)
S(-)
S(+)
2:
1:
PO
GND
Multi-functio n pulse
outp ut 32 kHz M ax.
P
CN3
Op ti on PG en cod er ca rd or
DC24 power card
*5
*5
*4
*6
*2
*5
(-10~10V/0~10V, 15KΩ, 4~20mA, 500Ω)
(0~10V, 200K)
SW5
*8
*3
(4~20mA, 500)
*8
P1
*5
SG
CN2
Op tion com m. car d or I/O
exp an sion card
ON
OFF
SW2SW1 SW3
SW4
AO2 AI1 AI2AO1
V
I
V
I
V
I
V
I
L1(R)
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 30HP or lower ratings have a built-in braking transistor. To use this braking
transistor a braking resistor can be connected between B1 and B2.
*2: Use SW6 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S8.
*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2).
Besides please also check parameter 04-00 for proper setting.
*4: Run Permissive input SF1 and SF2 is a normally closed input. This input should be closed to enable the inverter output.
To activate this input remove the jumper wire between SF1/ SF2 and SG.
*5: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*6: AO1/AO2 default setting is 0~+10V.
*7: Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*8: Only the model 200V 3~40HP and 400V 5~75HP provide P1 terminal, for external DCL connected between P1 and P2,
P1 and P2 are short-circuited before shipping out from the factory.
*9: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.