3-25
Type Terminal Terminal Function Signal Level / Information
Pulse input
signal
PI
Pulse command input,
Bandwidth: 32KHz
L: from 0.0 to 0.5V
H: from 4.0 to 13.2V
Max. Frequency: 0 - 32KHz
Built-in pull-up resistance.
When open collector input is
used, it is not required to
connect resistance.
GND
Analog signals ground terminal ----
Digital
output
DO1
Multi-function(open collector transistor)
output *1
48Vdc, 2mA ~50mA
Open-collector output
DO2
200V:1-2HP
400V:1-3HP
DOG
Open collector transistor digital ground
Relay
output
R1A
Relay A contact (multi-function output
terminal)
Relay B contact (multi-function output
terminal)
Relay contact common terminal,
With the same functions as DO1/DO2
Rating:
250Vac, 10 mA ~ 1A
30Vdc, 10 mA ~ 1A
R1B
R1C
R2A-R2C
200V:over
3HP
400V:over
5HP
With the same functions as DO1/DO2
Rating:
250Vac, 10 mA ~ 1A
30Vdc, 10 mA ~ 1A
Run
Permissive
Input
F1
On: normal operation.
Off: stop.
(Jumper wired between F1 and F2 has to be
removed by using external contact to stop.)
24Vdc, 8mA, pull-up
F2
24V Ground
RS-485
port
S (+)
RS485/ Modbus communication protocol Differential input and output
S (-)
Grounding
E (G)
Grounding to earth
Shield the connecting terminal
----
Notes:
*1:Multi-function digital input/ output can be referred to in this manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2:Multi-function analog input/ output can be referred to in this manual..
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.