Check / verify and alter parameters for remote start & remote frequency as
necessary before you proceed. Parameters 00-02 & 00-05
See quick start parameter list & How to alter parameters.
1) To run. Activate the remote run switch connected to terminals
S1 ( FWD) or S2 ( REV) as required. Parameter 00-02 = 1
The frequency will ramp up to the frequency set by one of the
following selections according to the set acceleration ramp time:-
x Potentiometer on the keypad Parameter 00-05 = 1
x External potentiometer. Parameter 00-05 = 2(AI1) or 3(AI2)
x External Analogue input Parameter 00-05 = 2(AI1) or 3(AI2)
2) To Stop. De-activate the remote run switch.
The frequency will ramp down to zero and according to the decel ramp
time.