Remote speed reference and Remote run
1) Ensure that you have carried out installation & wiring requirements as per
previous page before you proceed.
2) For analogue signals 2-10V / 0-10V dc or 0-20mA / 4-20 mA.dc. Use
either terminal AI1or AI2.
Check & set Jumper bars JP2&JP3 as required to position V (voltage)
or I ( current) as below:
V (Voltage) I (Current)
For remote potentiometer OR remote 2-10V / 0-10V dc signal use the
following terminals:
Terminal 10V. The supply provided for use with the potentiometer.
Terminal AI1 or AI2. Potentiometer wiper connection.
Terminal AGND. 0Vdc.
For 0-20mA / 4-20mA signals use the following terminals:
Terminal AI1 or AI2.
Terminal AGND. 0Vdc.
Step 1
Remote mode wiring. Speed reference .
Step 2
Remote mode Run
1) Remote Run signal can be either a PNP or NPN input type.
Set PNP or NPN selection as required by Jumper JP1 as shown below:
Note: PNP ( positive voltage switching) selection is recommended for use in EU.
PNP NPN
2) Connect remote start switch if required according to diagram in the
instruction manual.
Terminals 24V & S1 (Forward run)
Terminals 24V & S2 (Reverse run)
24V is the common terminal for PNP type inverters.
COM (0Vdc) terminal is common for the NPN type inverters.