EasyManua.ls Logo

TECO E510s Series - Page 12

TECO E510s Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Group 03: External Digital Input and Output
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
03-00
Multifunction
Input
Terminal S1
0: Forward/
Stop Command
0
1: Reverse/
Stop Command
2:Multi-Speed/
Position
Setting
Command 0
3:Multi-Speed/
Position
Setting
Command 1
4:Multi-Speed/
Position Setting
Command 2
5:Multi-Speed/
Position Setting
Command 3
6: Forward Jog
Run Command
03-01
Multifunction
Input
Terminal S2
7: Reverse Jog
Run Command
1
8: UP
Frequency
Increasing
Command
9: DOWN
Frequency
Decreasing
Command
10:Acceleration
/ Deceleration
Time
Selection 2
11: Inhibit
Acceleration/
Deceleration
Command
12: Main/
A
lternative Run
Switch
Function
13: Main/
Alternative
Frequency
Switch
Function
03-02
Multifunction
Input
Terminal S3
14: Emergency
Stop
(decelerate to
zero and stop)
2
15: External
Baseblock
Command
(rotation freely
to stop)
16: PID Control
Disable
17: Fault Reset
Group 03: External Digital Input and Output
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
18: Auto Run
Mode Enable
19: Speed
Search 1
20: Energy
Saving (V/F
o
nly)
03-03
Multifunction
Input
Terminal S4
21: Reset PID
integral value to
Zero t
3
22: Counter
Input
23: Counter
reset
24: PLC Input
25: Pulse-In
width
measure(S3)
26: Pulse-In
frequency
measure(S3)
03-04
Multifunction
Input
Terminal S5
27: Local/
Remote
Selection
4
28: Remote
Mode Selection
29: Jog
Frequency
Selection
33: DC Braking
03-05
Multifunction
Input
Terminal S6
34: Speed
Search 2
17
40: Switching
between Motor
1/ Motor 2
41: PID Sleep
47: Fire mode
48: KEB
Acceleration
57: Forced
Frequency Run
63: Switch to
Constant
Pressure 2
65: Short-circuit
Braking
66: PID Control
Disable 2
68: External
Fault
69: External
Overload
03-06
Up/Down
frequency
step
0.00~5.00