Group 03: External Digital Input and Output
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
03-07
Up/Down
Keep
Frequency
Status after
Stop
Command
0When
Up/Down is
used, the
preset
frequency is
held as the
inverter stops,
and the
UP/Down
function is
disabled
0
1When
Up/Down is
used, the
preset
frequency is
reset to 0 Hz as
the inverter
stops.
2
When
Up/Down is
used, the
preset
frequency is
held as the
inverter stops,
and the
UP/Down is
available.
3When
acceleration is
used, the
output
frequency will
be updated.
03-08
S1~S8 DI
Scan Time
1~200 1
03-09
Multi-Function
Terminal
S1-S4 Type
Selection
xxx0b:S1 A
Contact
xxx1b:S1 B
Contact
0000b
xx0xb:S2 A
Contact
xx1xb:S2 B
Contact
x0xxb:S3 A
Contact
x1xxb:S3 B
Contact
0xxxb:S4 A
Contact
1xxxb:S4 B
Contact
03-10
Multi-Function
Terminal S5~
S6 type
selection
xxx0b:S5 A
Contact
xxx1b:S5 B
Contact
0000b
Group 03: External Digital Input and Output
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
xx0xb:S6 A
Contact
xx1xb:S6 B
Contact
03-11
Relay
(R1A-R1C)
Output
0: During
Running
1
1: Fault Contac
t
Output
2: Frequency
Agree
3: Setting
Frequency
Agree
(03-13±03-14)
4: Frequency
Detection 1(
03-13+03-14)
5: Frequency
Detection 2(
03-13+03-14)
6: Automatic
Restart
7: Momentary
AC Power Loss
8: Rapid Stop
9: Base block
10: Motor
Overload
Protection
(OL1)
11: Drive
Overload
Protection
(OL2)
12: Over-torque
Threshold
Level (OT)
13: Preset
Output Current
Reached
14: Brake
Control
15: PID
Feedback
Signal Loss
16: Single
pre-set count
(3-22~23
17: Dual pre-se
t
count
(3-22~23)
18: PLC Status
Indicator
(00-02)
19: PLC
Control*
2
0: Zero Speed