Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Limit
08-42
PTC
Protection
Level
0.1~10.0V 0.7
08-43
PTC Restart
Level
0.1~10.0V 0.3
08-44
PTC Warning
Level
0.1~10.0V 0.5
08-46
Temperature
Agree Level
0~254°C 0
08-47
Temperature
Reset Level
0~254°C 0
08-48
Selection of
Fire Mode
0: Disable
1: Enable
0
08-49
Multi-Function
Input
Terminal
Status of Fire
Mode
0: Reset after
Power Off
1: Reset after
Power
Removed
0
08-50
Multi-Function
Terminal
Status of Fire
Mode
xxx0b: S6 A
Contact
xxx1b: S6 B
Contact
0000b
08-51
Motor Speed
SettingSSour
ce of Fire
Mode
0: Fire Mode
Speed (08-52)
1: PID Control
2: AI2
0
08-52
Motor Speed
of Fire Mode
0.00~100.00 100.00
08-53
PID Detection
Level of Fire
Mode
0~100 0
08-54
Delay Time of
Fire Mode
PID Loss
0.0~10.0 0.0
08-55
PID Feedback
Loss
Detection
Selection of
Fire Mode
0:Keep
Running
1:Fire Mode
Speed(08-52)
2:Max Output
Frequency
(01-02)
0
08-56
Detection
Level of Fire
Mode AI2
Signal
0~100 0
08-57
Delay Time of
Fire Mode AI2
Signal Loss
0.0~10.0 0.0
08-58
Selection of
Fire Mode AI2
Signal Loss
0:Keep
Running
1:Fire Mode
Speed(08-52)
2:Max Output
Frequency
(01-02)
0
08-59
Fire Mode
Motor
Detection
0:Forward
1:Reverse
0
08-60 Fire Mode 00000~65534 0
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Password
***STO function only be designed in EMC filter
built-in models.
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
09-00
INV
Communicati
on Station
Address
1~254 1 *3
09-01
Communicati
on Mode
Selection
0: MODBUS
0 *3
1: BACnet
3: PUMP in
Parallel
Connection
09-02
Baud Rate
Setting (bps)
2: 4800
4 *3
3: 9600
4: 19200
5: 38400
09-03
Stop Bit
Selection
0: 1 Stop Bit
0 *3
1: 2 Stop Bit
09-04
Parity
Selection
0: No Parity
0 *3 1: Even Bit
2: Odd Bit
09-05
Communicati
on Data Bit
Selection
0: 8 Bit Data
0 *3
1: 7 Bit Data
09-06
Communicati
on Error
Detection
Time
0.0~25.5 0.0 *3
09-07
Fault Stop
Selection
0: Deceleration
to Stop By
Deceleration
Time 1
3 *3
1: Coast to Stop
2: Deceleration
to Stop By
Deceleration
Time 2
3: Keep
Operating
09-08
Comm. Fault
Tolerance
Count
1~20 1 *3
09-09 Waiting Time 5~65 5 *3
09-10
BACNET
Device
Instance
Number
1~254 1
*3
*3: Parameter group 09 will not be effected by factory