21
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
10-00
PID Target
Value Source
Setting
0: Keypad
given
1
1: AI1 given
2: AI2 given
3: Communication
given
4: 10-02 given
10-01
PID Feedback
Value Source
Setting
0: Keypad
given
2
1: AI1 given
2: AI2 given
3: Communication
given
10-02
PID Target
Value
0.00~100.00 0.00 *1
10-03
PID Control
Mode
xxx0b: PID
Disable
0000b
xxx1b: PID
Enable
xx0xb: PID
Positive
Characteristic
xx1xb: PID
Negative
Characteristic
x0xxb: PID
Error Value of
D Control
x1xxb: PID
Feedback
Value of D
Control
0xxxb: PID
Output
1xxxb: PID
Output +
Frequency
Command
10-04
Feedback
Gain
0.01~10.00 1.00 *1
10-05
Proportional
Gain (P)
0.00~10.00 1.00 *1
10-06
Integral Time
(I)
0.00~100.00 1.00 *1
10-07
Differential
Time (D)
0.00~10.00 0.00 *1
10-08
Primary Delay
Filter Time
1~250 4 *1
10-09 PID Bias -100.0~100.0 0 *1
10-11
PID Feedback
Loss
Detection
Selection
0: Disable
0
1: Warning
2: Fault
10-12
PID Feedback
Loss Det. Lev.
0~100 0
10-13
PID Feedback
Loss Det.
Time
0.0~25.5 1.0
10-14 PID Integral 0.0~100.0 100.0 *1
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Limit
10-17
*Start
Frequency of
PID Sleep
0.00~599.00 0.00
10-18
Delay Time of
PID Sleep
0.0~255.5 0.0
10-19
*Frequency of
PID Waking
up
0.00~599.00 0.00
10-20
Delay Time of
PID Waking
up
0.0~255.5 0.0
10-21 Reserved
10-22 Reserved
10-23
PID Output
Limit
0.00~100.0 100.0 *1
10-24
PID Output
Gain
0.0~25.0 1.0
10-25
PID Reversal
Output
Selection
0: No Allowing
Reversal
Output
0
1: Allow
Reversal
Output
10-26
PID Target
Acceleration/
Deceleration
Time
0.0~25.5 0.0
10-27
PID Feedback
Display Bias
-99.99~99.99 0
10-29
PID Sleep
Selection
0: Disable
1 1: Enable
2: set by DI
10-30
Upper Limit of
PID Target
0.0 ~ 100.0 100.0
10-31
Lower Limit of
PID Target
0.0 ~ 100.0 0.0
10-33
Maximum
Value of PID
Feedback
1 ~ 10000 999
10-34
PID Decimal
Width
0 ~ 4 1
10-35 PID Unit
0: %
0 *7
1: FPM
2: CFM
3: SPI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM