22
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: kPa
10-39
*Output
Frequency
Setting of PID
Disconnection
00.00~599.00 30.00
10-40
Selection of
PID Sleep
Compensatio
n Frequency
0: Disable
0
1: Enable
10-47
Proportional
Gain (P) of
Fire Mode
0.00~10.00 1.00 *1
10-48
Integral Time
(I) of Fire
Mode
0.00~100.00 1.00 *1
10-49
Differential
Time (D) of
Fire Mode
0.00~10.00 0.00 *1
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-00
Direction Lock
Selection
0: Allow
Forward and
Reverse
Rotation
0
1: Only Allow
Forward
Rotation
2: Only Allow
Reverse
Rotation
11-01
Carrier
frequency
0: Carrier
Output
Frequency
Tuning
1~16: 1~16KHz
*
11-02
Soft PWM
Function
Selection
0: Disable
0
1: Soft PWM
11-03
Automatic
carrier
lowering
selection
0: Disable
0
1: Enable
11-04
S-curve Time
Setting at the
Start of
Acceleration
0.00~2.50 0.20
11-05
S-curve Time
Setting at the
0.00~2.50 0.20
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Stop of
Acceleration
11-06
S-curve Time
Setting at the
Start of
Deceleration
0.00~2.50 0.20
11-07
S-curve Time
Setting at the
Stop of
Deceleration
0.00~2.50 0.20
11-08
Jump
Frequency 1
0.0~599.0 0.0
11-09
Jump
Frequency 2
0.0~599.0 0.0
11-10
Jump
Frequency 3
0.0~599.0 0.0
11-11
Jump
Frequency
Width
0.00 ~ 25.5 1.0
11-12
Manual
Energy
Saving Gain
(V/F)
0~100 80
11-14
OV
Prevention
Selection
230V: 200V~400V
400V: 400V~800V
370
740
11-17
Acceleration/
Deceleration
Gain
0.1~10.0 1
11-18
Manual
Energy
Saving
Frequency
0.0~599.0 0.0
11-28
Frequency
Gain of Over
Voltage
Prevention 2
1~200 100
11-33
DC Voltage
Filter Rise
Amount
0.1~10.0 0.1
11-34
DC Voltage
Filter Fall
Amount
0.1~10.0 5.0 *1
11-35
DC Voltage
Filter
Deadband
Level
0.0~99.0 10.0 *1
11-36
Frequency
gain of OV
Prevention
0.000~1.000 0.050 *1
11-37
Frequency
limit of OV
Prevention
*0.00~599.00 5.00 *1
11-38
Deceleration
start voltage
of OV
prevention
200V:
200~400V
300
400V:
400~800V
700
11-39
Deceleration
end voltage of
OV
Prevention
200V:
300~400V
350
400V:
600~800V
750