23
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-40
OV
Prevention
Selection
0~3 0
11-47
KEB
Deceleration
Time
0.0~25.5 0.0 *1
11-48
KEB
Detection
Level
230V: 190~210 200V
400V: 380~420 400V
11-55
STOP Key
Selection
0: Stop Key is
Disabled when
the Operation
Command is
not Provided
by Operator.
1
1: Stop Key is
Enabled when
the Operation
Command is
not Provided
by Operator.
11-59
Gain of
Preventing
Oscillation
0.00~2.50 *
11-60
Upper Limit of
Preventing
Oscillation
0~100 *
11-61
Time
Parameter of
Preventing
Oscillation 1
0~100 0
11-62
Selection of
Preventing
Oscillation
0: Mode 1
1 1: Mode 2
2: Mode 3
11-63
Strong
Magnetic
Selection
0: Disable
1
1: Enable
11-69
Gain of
Preventing
Oscillation 2
0.00~200.00 5.00
11-70
Upper Limit of
Preventing
Oscillation 2
0.01~100.00 5.00
11-71
Time of
Preventing
Oscillation 2
0~30000 100
11-72
Switch
Frequency 1
of Preventing
Oscillation 2
0.01~300.00 30.00
11-73
Switch
Frequency 2
of Preventing
Oscillation 2
0.01~300.00 50.00
* If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to
0.1Hz.
Note: The parameter of 11-01 can be changed
during run operation, the range is 1~16KHz.
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
12-00
Display
Screen
Selection
(LED)
00000~88888
From the
leftmost bit, it
displays the
screen when
press DSP key
in order.
0: no display
1: Output
Current
2: Output
Voltage
3: DC Bus
Voltage
4: Heatsink
Temperature*
5: PID
Feedback
6: AI1 Value
7: AI2 Value
8: Counter
Value
00000
*1
*6
12-01
PID Feedback
Display Mode
(LED)
0: Display the
Feedback
Value by
Integer (xxx)
0 *6
1: Display the
Feedback
Value by the
Value with One
Decimal Place
(xx.x)
2: Display the
Feedback
Value by the
Value with Two
Decimal
Places (x.xx)
12-02
PID Feedback
Display Unit
Setting (LED)
0: xxxxx (no
unit)
0 *6
1: xxxPb
(pressure)
2: xxxFL (flow)
12-03
Line Speed
Display (LED)
0~60000
1500/
1800
*1
*6
12-04
Modes of Line
Speed
Display (LED)
0: Display
Inverter Output
Frequency
0
*1
*6
1: Display Line
Speed with
integer (xxxxx)
2: Display Line
Speed with the
First Decimal
Place (xxxx.x)
3: Display Line
Speed with the
Second
Decimal Place
(xxx.xx)