LED display Possible solutions
OCd
over current
Set the longer acceleration
time
GF
Ground fault
Replace motor.
Check the motor wiring.
Disconnect motor and try
running inverter.
Check resistance between
cables and ground.
Reduce carrier frequency.
OV
Over voltage
Increase deceleration time
Reduce input voltage to
comply with the input voltage
requirements or install an AC
line reactor to lower the input
voltage.
Remove the power factor
correction capacitor.
Use dynamic braking unit.
Replace braking transistor or
resistor.
Adjust speed search
parameters.
LV
Low Voltage
Check the input voltage.
Check input wiring.
Increase acceleration time.
Check power source
Replace pre-charge
contactor
Replace control board or
complete inverter.
IPL input phase
loss
Check input wiring / faster
screws.
Check power supply.
OPL output
phase loss
Check output wiring / faster
screws.
Check motor & inverter
rating.
OH1
Heatsink
overheat
Install fan or AC to cool
surroundings.
Replace cooling fan.
Reduce carrier frequency.
Reduce load / Measure
output current
OH4
Motor overheat
Check the surrounding
temperature of motor.
Check the MT and GND
terminal wiring be correct
OL1
Motor
overload
Check V/f curve.
Check motor rated current
Check and reduce motor
load, check and operation
duty cycle.
OL2
Inverter
overload
Check V/f curve.
Replace inverter with larger
LED display Possible solutions
rating.
Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
Check over torque detection
parameters (08-15 / 08-16).
Check and reduce motor
load, check and operation
duty cycle.
CE
communication
error
Check connection
Check host computer /
software.
FB
PID feedback
loss
Check feedback wiring
Replace feedback sensor.
PO
Voltage Off
Check SF1 and SG
connection
STO 1
Safety 1 Error
Check SF1 and SG
connection.
PO2
Voltage Off
Check SF2 and SG
connection
STO2
Safety 2 Error
Check SF2 and SG
connection.
PO3
Voltage Off
Replace the power board
Contact with TECO
STO3
Safety 3 Error
Replace the power board
Contact with TECO.
EF0
External fault 0
Reset Modbus
communication 0x2501 bit
2= "1"
EF1
External
Fault(S1)
Multi-function input function
set incorrectly.
Check wiring
EF2
External Fault
(S2)
EF3
External Fault
(S3)