51
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
0: VF
1: PG
2: SLV
3: SV
4: PSV
5: PMSLV
6: SLV2
12-25 AI1 Input
Display the
current Al1 input
(-10V
corresponds to -
100%, 10V
corresponds to
100%)
-
12-26 AI2 Input
Display the
current Al2 input
(0V or 4mA
corresponds to
0%, 10V or
20mA
corresponds to
100%)
-
12-27 Motor Torque
Display the
current torque
command
(100%
corresponds to
motor torque )
-
12-28
Motor Torque
Current (Iq)
Display the
current q-axis
current
-
12-29
Motor
Excitation
Current (Id)
Display the
current d-axis
current
-
12-30 ASR Deviation
Display deviation
of speed
controller (speed
command -
speed feedback)
(100%
corresponds to
the maximum
frequency set by
01-02 )
-
12-31 Reserved
12-32 ASR Output
Display output
value of speed
controller
(100%
corresponds to
the maximum
frequency set
by 01-02)
-
12-33 PG Feedback
Display
feedback’s
speed value of
speed
controller
(100%
corresponds to
the maximum
-
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
frequency set
by 01-02)
12-34
PG Pulse
Number
Display PG
pulse number
of speed
controller
- Note4
12-35
Zero-servo
Pulse Number
When display SV
position mode,
the position error
pulse number of
the zero speed
servo (the pulse
number of a
circle is four
times of set
values of 20-27)
-
12-36 PID Input
Display input
error of the PID
controller (PID
target value - PID
feedback)
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-37 PID Output
Display output of
the PID controller
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-38 PID Setting
Display the target
value of the PID
controller
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-39 PID Feedback
Display the
feedback value
of the PID
controller
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-40 Reserved
12-41
Heatsink
Temperature*
Display the
heatsink
temperature of
IGBT
temperature**
*
12-42
RS-485 Error
Code
0000 0000
1: CRC Error
1: Data length Error
1: Data Function Error
1: Parity Error
1: Overrun Error
1: Framing Error
1: Time out Error
Rese rved
-