70
LED display Corrective action
STP2
External
Terminal Stop
Error
Remove the run
command from external
terminal
EnC
Encoder Error
Check encoder wiring
17-07 PG pulse number
setting is not
corresponding to the
encoder.
Replace the encoder.
RunEr
Wrong running
direction Error
Revise the command
among 11-00, jog and
DI control to see if any
difference
PArEr
Parameter
setting error
Please refer to our
instruction manual for
correct setting
STP1
Direct start
warning
Remove the run
command from the
terminal first, and
enabled later.
FirE
Fire mode
enabled
Check the environment
and confirm the fire
status. If no fire, turn off
the power and power on
again.
AdCEr
Voltage on C/B
error
Check the voltage on
the control board.
EPErr
EEPROM Save
error
Restore factory setting,
then cut off the power
and power on again.
If warning again,
replace control board.
bdErr
Control board
error
Replace the control
board.
LED display Corrective action
Parameter
Lock
Lifting the parameter
lock key code, to enter
the correct parameter
for 13-07
Set password
failed
Enter the correct
parameter for 13-07 to
enable the parameter
lock key
CYErr
Capacitor error
Replace the capacitor
and ask the original
dealer reset the counter
in inverter
FILFE
Fan life error
Replace the fan and ask
the original dealer reset
the counter in inverter
ILIFE
IGBT life error
Replace the IGBT and
ask the original dealer
reset the counter in
inverter
4.4 Auto-tuning Error
When a fault occurs during auto-tuning of a
standard AC motor, the display will show the
“AtErr” fault and the motor stops. The fault
information is displayed in parameter 17-11.
Note: The fault contact output does not
energize with an auto-tuning fault. Refer to
Table 4.3, for fault information during tuning,
cause and corrective action.
Table 4.3 Auto-tuning fault and corrective
actions
Error Corrective action
01
Motor data input
error.
Check the motor tuning
data (17-00 to 17-09).
Check inverter capacity
02
Motor lead to
lead resistance
R1 tuning error.
Check the motor tuning
data (17-00 to 17-09).
Check motor connection.
Disconnect motor load.
Check inverter current
detection circuit and
DCCTs.
03
Motor leakage
inductance
tuning error.