FM50(TW/ E2)- START GUIDE                10
Running Three Phase Motors from 
"Single Phase 240V" Inverters. 
If your motor was originally wired to an industrial three phase supply, it 
is likely that the motor voltage is wired for 415V. The inverter will run 
the motor without harm, but the torque will be a fraction of what it 
should be. 
 
Here's how to check, and if necessary change the motor wiring. 
 
On the left is a typical TECO MAX-E2 motor 
rating plate. In the 50Hz box of data you will 
see a voltage rating "220-240V 
/ 380-415V 
". This information tells us that the motor can 
be wired for two voltage ranges. 
 
In the 
 or Delta configuration, the motor will 
run on a three phase supply from 220V to 240V 
phase to phase.  
 
In the 
 or Star configuration, the motor will 
run on a three phase supply from 380V to 415V 
phase to phase.
 
 
How to determine the motor configuration? 
 
Connection
 
On the left is a typical TECO & MONARCH motor terminal arrangement. 
The drawing shows the Star configuration. The three wires from the 
Inverter output terminals directly to the U1, V1 and W1 leads. The other 
three leads W2, U2 and V2 are linked together often with a set of brass 
stampings or strips. Wires are also used to make the circuit. For small 
motor (*Notes) this star connection would be consistent with 415V 
operation. 
*Notes: The TECO small motor is 4Kw & below. 
              The MONARCH small motor is 3Kw & below.
 
The motor terminals shown on the right are wired in a Delta configuration. 
The brass strips, used to make the star connection above, are simply 
removed and rearranged. 
To find out a spare strip to make the third connection. 
Wires the inverter go directly to the U1, V1 and W1 leads as usual. In the 
Delta case the connections will share the terminal U1 and W2, V1 and U2, 
W1 and V2 with the brass strip.
 The small motor is now wired for 240V 
operation.
 
Connection