11
Frame3&Frame4
Terminal symbols TM1 Function Description
RA
Relay output terminal, Specification: 250VAC/5A(30VDC/5A)
RA: Normally open RB: Normally close RC: common point
RB
RC
Terminal
symbols
TM2 Function Description Signal Level
+24V Common point of PNP input
±15%,Max output current 30mA
SC
NPN/PNP selectable terminal.
NPN input: +24V&SC need to be shorted.
PNP input: COM&SC need to be shorted.
COM voltage reference point for S1~S5
S1~S5
Multi-function input terminals(refer to
group3)
24 VDC, 4.5 mA, Optical coupling
isolation (Max,voltage30 Vdc,
Input impedance 6kΩ)
10V
Built in Power for an external speed
potentiometer (Max output : 20mA)
10V,(Max current:20mA)
AVI/PTC
Analog voltage input/motor over
temperature protection signal input,
Specification : 0~10VDC
0~10V(Input impedance 200kΩ)
ACI
Analog current input, Specification :
0~20mA / 4~20mA(choose by parameter
04-00)
0~20mA(Input impedance 249Ω)
AO
Multi function analog output terminal.
Maximum output 10VDC/1mA
0~10V(Max current 2mA)
AGND Analog ground terminal
NPN/PNP: