18
Group 06- Auto Run(Auto Sequencer)
function
No. Description Range
Factory
Setting
Note
06-16
A
uto_ Run
Mode
running time
s
etting 0
0.0 ~ 3600.0
0.0 *1
06-17
A
uto_ Run
Mode
running time
s
etting 1
0.0 *1
06-18
A
uto_ Run
Mode
running time
s
etting 2
0.0 *1
06-19
A
uto_ Run
Mode
running time
s
etting 3
0.0 *1
06-20
A
uto_ Run
Mode
running time
s
etting 4
0.0 *1
06-21
A
uto_ Run
Mode
running time
s
etting 5
0.0 *1
06-22
A
uto_ Run
Mode
running time
s
etting 6
0.0 *1
06-23
A
uto_ Run
Mode
running time
s
etting 7
0.0 *1
06-24
~
06-31
Reserved
06-32
A
uto_ Run
Mode
running
d
irection 0
0: Stop
1: Forward
2
: Reverse
0
06-33
A
uto_ Run
Mode
running
d
irection 1
0
06-34
A
uto_ Run
Mode
running
d
irection 2
0
06-35
A
uto_ Run
Mode
running
d
irection 3
0
06-36
A
uto_ Run
Mode
running
d
irection 4
0
06-37
A
uto_ Run
Mode
running
d
irection 5
0
Group 06- Auto Run(Auto Sequencer)
function
No. Description Range
Factory
Setting
Note
06-38
A
uto_ Run
Mode
running
d
irection 6
0
06-39
A
uto_ Run
Mode
running
d
irection 7
0
Group 07- Start/Stop command setup
No. Description Range
Factory
Setting
Note
07-00
Momentary
Power Loss
and Restart
0: Momentary
Power Loss and
Restart disable
1: Momentary
power loss and
restart enable
0
07-01
A
uto Restart
Delay Time
0.0~800.0 0.0
07-02
Number of
A
uto Restart
A
ttempts
0~10 0
07-03
Reset Mode
Setting
0: Enable Reset
Only when Run
Command is Off
1: Enable Reset
w
hen Run
Command is On or
Off
0
07-04
Direct
Running
A
fter Power
Up
0: Enable Direct
run on power up
1: Disable Direct
run on power up
1
07-05
Delay-ON
T
imer
1.0~300.0 1.0
07-06
DC Injection
Brake Start
Frequency
(Hz) In Stop
mode
0.10 ~ 10.00 1.5
07-07
DC Injection
Brake Level
(%) In stop
mode
0 ~ 20 (Frame1/2).
Based on the 20%
o
f maximum outpu
t
v
oltage 5
0 ~ 100 (Frame3/4)
based on the rated
current 50
07-08
DC Injection
Brake Time
(Seconds)
In stop
mode
0.0 ~ 25.5 0.5
07-09
Stopping
Method
0: Deceleration to
s
top
1: Coast to stop
0
07-10
DC Braking 0~100 0