20
Group 08- Drive & Motor Protection
functions
No. Description Range
Factory
Setting
Note
w
hen protection
level is reached.
08-11
PTC Signal
Smoothing
T
ime
0.01~10.00 0.2
08-12
PTC
Detection
T
ime Delay
1~300 60
08-13
PTC
Protection
Level
0.1~10.0 0.7
08-14
PTC
Detection
Level Rese
t
0.1~10.0 0.3
08-15
PTC
W
arning
Level
0.1~10.0 0.5
08-16
Fan Control
T
emperatur
e Level
10.0~50.0 50.0
08-17
Over current
protection
level
0.0 ~ 60.0 0.0
08-18
Over current
protection
t
ime
0.0 ~ 1500.0 1.0
08-19
Motor
Overload
Protection
Level
0: Motor Overload
Protection Level 0
1: Motor Overload
Protection Level 1
2
: Motor Overload
Protection Level 2
0
Group 09- Communication function
setup
No. Description Range
Factory
Setting
Note
09-00
A
ssigned
Communica
t
ion
Station
Number
1 ~ 32 1 *2*3
09-01
Communica
t
ion Mode
Selec
t
0: Modbus RTU
code
1: Modbus ASCII
code
2
: BACnet
0 *2*3
09-02
Baud Rate
Setting
(bps)
0 :4800
1: 9600
2
: 19200
3: 38400
2 *2*3
09-03
Stop Bit
Selection
0: 1 Stop Bit
1: 2 Stop Bits
0 *2*3
09-04
Parity
Selection
0: Without Parity
1: With Even Parit
y
2
: With Odd Parity
0 *2*3
Group 09- Communication function
setup
No. Description Range
Factory
Setting
Note
09-05
Data Forma
t
Selection
0: 8-Bits Data
1: 7-Bits Data
0 *2*3
09-06
Communica
t
ion time-out
d
etection
t
ime
0.0 ~ 25.5 0.0
09-07
Communica
t
ion time-out
o
peration
s
election
0: Deceleration to
s
top (00-15:
Deceleration time 1)
1: Coast to stop
2
: Deceleration to
s
top (00-17:
Deceleration time 2)
3: continue
o
perating
0
09-08
Error 6
v
erification
t
ime.
0 ~ 20 3
09-09
Drive
T
ransmit
d
elay Time
ms
5 ~ 65 5
09-10
BACnet
s
tations
1~254 1 *2*3
Group10- PID function Setup
No. Description Range
Factory
Setting
Note
10-00
PID target
v
alue
s
election
(when
00-05\00-06
=6
,this function
is enabled)
0: Potentiometer
o
n Keypad
1: Analog Signal
Input. (AVI)
2
: Analog Signal
Input. (ACI)
3: Frequency set
by communication
4
: KeyPad
Frequency
parameter 10-02
5: Preset
f
requenc
y
1 *1
10-01
PID
f
eedback
v
alue
s
election
0: Potentiometer
o
n Keypad
1: Analog Signal
Input. (AVI)
2
: Analog Signal
Input. (ACI)
3: Communication
Setting Frequenc
y
2 *1
10-02
PID Target
(keypad
input)
0.0~100.0 50.0 *1
10-03
PID Mode
Selection
0: Disabled
1: Deviation D
Control. FWD
Characteristic.
0