4.  If either of following situations should develop, the auto restart times will be reset: 
(1)  No additional malfunction (in operation or stop) occurs within 10 minutes. 
(2)  Press RESET button. 
 
 
F_25: Return to Factory Pre-Settings  
= 010: Constants initialization to 50Hz system 
= 020: Constants initialization to 60Hz system 
 
1.  When F_25 is set to 010, all parameters are restored to factory settings. The settings of F_05 =1 
and F_06 = 50. F_25 is restored back to 000 after the reset process is complete. (50Hz operation) 
 
2. When F_25 is set to 020, all parameters are restored to factory settings. The settings of F_05 =4 and 
F_06 = 60. F_25 is restored back to 000 after the reset process is complete. (60Hz operation) 
 
 
F_26: SP2(1~200Hz) , Multi-speed2 (Reference to F_19 ﹠F_20) 
 
F_27: SP3(1~200Hz) , Multi-speed3 (Reference to F_19 ﹠F_20) 
 
F_28: Direct start 
= 0 : Direct start enable when remote Run command on 
= 1 : Direct start disable when remote Run command on 
(CPU version V2.1 and above) 
 
When F_28 = 1 and control mode is remote control (F_10 = 1), Inverter can not start if RUN switch is ON 
when power is engaged, Must be turned the RUN switch OFF and turned ON again, Then Inverter can 
start.