17
 
 
Inverter terminal descriptions 
 
Primary Circuitry Terminal Block (TM1) descriptions 
Terminal Symbol  Function Description 
L1(R) 
L2 (S) 
L3 (T) 
Primary power source input to Drive  
Single phase: L1/L2(1P2~201) or L/N; Three phase: L1/L2/L3 
P 
R 
Extermal braking resistor terminal (Only for E2-202/203/401/402/403)
T1 (U) 
T2 (V) 
T3 (W) 
Inverter output to Motor 
 Tightening torque for TM1 is 1 LBS-FT or 12 LBS-IN (1P2/1P5/101/2P2/2P5/201). 
 Tightening torque for TM1 is 1.3 LBS-FT or 16 LBS-IN (202/203/401/402/403). 
* Wire voltage rating must be a minimum of 300V (200V series)/600V (400V series) 
 
Control Circuitry Terminal Block (TM2) description 
Terminal Symbol  Function Description 
1 
2 
TRIP 
RELAY 
Fault relay output terminal ﹠Multi function output terminal (refer to F_21) 
Connection point rated capacity 250VAC/1A   (30VDC / 1A) 
3 FWD (FW) 
4 REV (RE) 
Operation control terminals (refer to F_03) 
5  + 12V(12)  Common point of terminal 3 / 4 / 6 / 7  
6 SP1(SP) 
7 RESET(RS) 
Multifunction input terminals (refer to F_19) 
8  +10V  Power terminal for potentiometer ( Pin 3 ) 
9 
Analog input wire 
Wiper 
Analog frequency signal input terminal ( Pin 2 of 
potentiometer or positive terminal of 0~10V / 4~20mA /
0~20mA) 
10 
 
0V(FM -) 
Analog common point 
nalog signal common point ( Pin 1 of potentiometer or 
negative terminal of 0~10V / 4~20mA / 0~20mA ) 
11 FM+ 
Analog output positive 
connection point 
Analog frequency signal output terminal 
Output terminal signal is 0 ~ 10VDC/Fn6 
 Tightening torque for TM2 is 0.42 LBS-FT or 5.03 LBS-IN. 
* Wire voltage rating must be a minimum of 300V 
* Control wiring should not run in the same conduit or raceway with power or motor wiring 
* Single Input and Output Terminals (TM2) Ratings are ALL Class 2