Fn_44: Stopping Mode and Braking Resistor Protection
xxx0 : Decel. to stop
xxx1 : Free fun to stop
xx0x : Braking resistor overheat protection disable
xx1x : Braking resistor overheat protection enable
Note:
If the (Fn_44) is set at free run to stop, the T-verter will cut off the output after receiving a stop
instruction and the motor will coast to a stop.
If the (Fn_44) is set for deceleration to stop, the T-verter will decelerate to the frequency set by
(Fn_54) after receiving deceleration instructions, the output voltage level set at (Fn_55) the
T-verter will stop after the time period set by (Fn_53)
If the (Fn_44) is set for protection of the Built-in braking transistor, and operation of drive is too
frequently decelerate, the braking transistor and braking resistor may overheat and T-verter will
trip. OH1 will show this on Keypad display. The T-verter can be manually restarted after the
braking resistor has cooled off. If the braking resistor is damaged and leads to OV-C trip,
deceleration time must be increased or the external braking resistor replaced.
Fn_45: Adjustment for Analog out put for Meters
Fn_46: Multi-function Analog output Meter Selection 0 - 3
0: Output freq.(Fn_06 max) : 10Vdc / (Fn_06)
1: Set frequency (Fn_06 max): 10Vdc / (Fn_06)
2: Output voltage (Vac) : 10Vdc / (Fn_30)
3: DC voltage :(10Vdc / 450 Vdc: for 200V series)
(10Vdc / 900 Vdc: for 400V series)
Fn_47: Meter Display Mode
xxx0 : Output Voltage display disable
xxx1 : Output Voltage Display enable
xx0x : DC Voltage Display disable
xx1x : DC Voltage Display enable
x0xx : Output Current disable
x1xx : Output Current enable (Meters)