c: (Fn_10) and (Fn_11) will be ineffective for T-verter operation and frequency control while
in the communication mode.
d: The frequency signals upper and lower limits are controlled by (Fn_06) (Fn_07) while in the
communication mode.
e: The PC will request data from the T-verter automatically to obtain information on the
(STATUS_LED, Vac, Vpn, Iac, Freq., RPM)
f: The T-verter will confirm the validity of the new parameters when set by the PC.
g : Please refer to the communications manual for the RS-232 and RS-485-for detail function
and protocol information.
Fn_123: Return Drive to Factory Settings:
(1111) Returns Drive to Factory settings for 60Hz operation:
(1110) Returns Drive to Factory settings for 50Hz operation:
Fn_124: CPU Software Version:
FN-125: Fault Log: Last 3 Faults
In order to simply any troubleshooting, The T-verter memorizes the last three fault codes
automatically in its EEPROM memory. Pressing the up & down arrows on the key-pad to review
the faults recorded.
Sample:
1. (LV-C) The first fault code (the newest) is low voltage
2. (OC-d) Over current during deceleration
3. (- - - -) No fault recorded (only two faults occurred)